This SVK water chiller was having a pump water flow issue.
The unit was cycling on low pressure turning the whole unit on and off, not just the compressor.
SOLUTION
F&R attended site and found a leak on the suction line elbow.
Engineer recovered the refrigerant and brazed over the fracture. Pressure tested with nitrogen and evacuated to a deep vacuum. Recharged with refrigerant.
Chiller now operating correctly.
RESULTS
✓ Chiller now working correctly
✓ Customer’s production back to normal
✓ Another happy customer
SEE BEFORE & AFTER PHOTOS BELOW